Skip to main content
Sparky

Earthing & Bonding

Upgrade your property's earthing and bonding to current standards. Main bonding, supplementary bonding, and earth electrode installation. Qualified and insured.

Get a quote
Book earthing & bonding online
Electrician

Earthing & Bonding

Qualified electrician

Book Now

Same-day service

Most jobs matched within hours.

Upfront pricing

Clear quotes before work starts.

Qualified pros

NICEIC & NAPIT registered.

Pay when done

Funds held until you're happy.

How it works

1

Earthing system assessment

The electrician identifies your earthing arrangement (TN-S, TN-C-S/PME, or TT) by inspecting the incoming supply and measuring the earth fault loop impedance. They check the condition and size of the main earthing conductor and all bonding conductors. Any deficiencies are recorded.

2

Main bonding installation or upgrade

10mm² main bonding conductors are installed (or existing ones replaced) from the main earthing terminal to the gas, water, and oil service entry points. Connections are made with BS 951 bonding clamps within 600mm of the point of entry. Labels are fitted at each bond.

3

Supplementary bonding

Where required (typically in bathrooms and where simultaneous contact with earthed metalwork and extraneous conductive parts is possible), 4mm² supplementary bonding conductors are installed between exposed metalwork — pipes, radiators, baths, and shower trays.

4

Earth electrode installation (TT systems)

For properties on a TT earthing system (no earth provided by the DNO), an earth rod is driven into the ground and connected to the main earthing terminal. The electrode resistance is measured and must be low enough for the RCD to operate within the required time.

5

Testing and verification

All earth fault loop impedances are measured, bonding continuity is verified, and RCD trip times are tested. The electrician confirms that all protective devices will disconnect within the time limits specified by BS 7671. An Electrical Installation Certificate or Minor Works Certificate is issued as appropriate.

What's included

Assessment of existing earthing arrangement (TN-S, TN-C-S, or TT)
Installation or upgrade of main earthing conductor (typically 16mm²)
Main protective bonding to gas, water, and oil services (10mm²)
Supplementary bonding in bathrooms and kitchens where required (4mm²)
BS 951 bonding clamps and warning labels at all connections
Earth rod installation for TT systems (where applicable)
Earth fault loop impedance testing on all circuits
Bonding continuity verification
Electrical Installation Certificate or Minor Works Certificate

What's involved

Earthing and bonding are fundamental safety measures in every electrical installation. The earthing system provides a path for fault current to flow safely to earth, causing protective devices (fuses, MCBs, RCDs) to disconnect the supply. Bonding connects all metallic services (gas, water, oil pipes) to the earthing system, preventing dangerous voltage differences between them. An earthing and bonding upgrade brings these systems up to the current BS 7671 standard — replacing undersized conductors, adding missing bonds, and ensuring the earth fault loop impedance is low enough for protective devices to operate within the required time.

Inadequate earthing and bonding is one of the most common defects found on EICRs. Without proper earthing, a fault on an appliance or circuit may not trip the protective device, leaving the metalwork live and creating a serious shock hazard. Without bonding, metallic pipes can carry dangerous voltages — particularly in bathrooms where the risk of electric shock is highest. If your EICR has flagged earthing or bonding deficiencies (C1 or C2 codes), this work is essential for safety. It is also required as part of consumer unit upgrades, rewires, and new circuit installations.

Get a personalised quote

Typical cost: £150–£500per property

Every job is different — pricing depends on your property, location, and specific requirements. Describe what you need and a qualified electrician will quote you directly.

How long does it take?

1-3 hours for main bonding upgrades on a straightforward property. Half a day if supplementary bonding, earth conductor replacement, or earth rod installation is also needed. Complex properties with long pipe runs or difficult access may take a full day.

Regulations & safety

Safety notice

Never remove or disconnect an existing bonding conductor — even temporarily. If a bonding conductor is disconnected while a fault exists elsewhere in the installation, metallic pipes can become live and create a lethal shock hazard.

Earthing and bonding work must be carried out by a qualified electrician. Incorrect connections — particularly connecting to the wrong pipe or using undersized conductors — can make the installation more dangerous rather than safer.

If you have a TT earthing system (common in rural properties), the earth rod provides your only earth path. It must be installed correctly and tested regularly. A poorly installed earth rod gives a false sense of security.

BS 7671:2018+A2:2022 — Chapter 54 (Earthing Arrangements and Protective Conductors)

Specifies the requirements for earthing arrangements, main earthing terminals, earthing conductors, protective bonding conductors, and earth electrodes. Defines the minimum conductor sizes and connection methods.

BS 7671:2018+A2:2022 — Regulation 411 (Automatic Disconnection of Supply)

Requires that the earthing system provides a sufficiently low impedance path for fault current to flow, enabling protective devices to disconnect the supply within 0.4 seconds (for socket circuits) or 5 seconds (for fixed equipment circuits).

Part P of the Building Regulations

Earthing and bonding work that involves the main earthing terminal or is carried out as part of a consumer unit upgrade or new circuit installation is notifiable. Standalone bonding upgrades may be covered by a Minor Works Certificate.

Electricity Safety, Quality and Continuity Regulations 2002 (ESQCR)

Governs the DNO's responsibility to provide an earthing facility (where available) and the requirements for connection at the supply intake. Relevant when the earthing arrangement involves the DNO's infrastructure.

What to expect

Earthing and bonding deficiencies are the most common reason for an EICR to fail. The good news is that bonding upgrades are relatively inexpensive — often £150-300 for main bonding alone. This is one of the highest-safety-value improvements you can make.
In older properties, the main bonding is often undersized (6mm² instead of the required 10mm²) or missing entirely. This is a C2 or even C1 code on an EICR. The fix is straightforward — a qualified electrician can upgrade the bonding in 1-2 hours.
Supplementary bonding in bathrooms can sometimes be omitted if the main bonding is in place and all circuits are RCD protected. Your electrician will assess whether supplementary bonding is required based on the specific installation conditions.
Properties with plastic water and gas pipes may have fewer bonding requirements, but the main bonding must still be connected at the point where metallic pipes enter the building — even if the internal pipework is plastic.
If your earthing type is unclear (especially in older properties that have been modified), the electrician will need to determine the correct arrangement before any work begins. This may require inspection at the meter position and testing at various points.

Frequently asked questions

What is the difference between earthing and bonding?
Earthing provides a safe path for fault current to flow to earth, causing the circuit breaker or fuse to trip. Bonding connects all metallic services (gas, water, oil pipes) to the same earthing point, so there cannot be a dangerous voltage difference between them. Both are essential for electrical safety — earthing protects you from faulty appliances, bonding protects you from faults on other people's installations reaching you through shared metalwork.
Why has my EICR failed on bonding?
The most common reasons are: main bonding conductors are missing or undersized (6mm² instead of 10mm²), bonding clamps are corroded or missing, bonding is connected to the wrong pipe (e.g., after the meter instead of before it), or supplementary bonding is missing in bathrooms. These are all fixable and relatively inexpensive.
What is a TT earthing system and why does it matter?
A TT system means the DNO does not provide an earth connection — your property relies on its own earth rod driven into the ground. This is common in rural areas. TT systems require an RCD on every circuit because the earth fault loop impedance is much higher. If you are on a TT system, the earth rod condition is critical to your safety.
Do plastic pipes need bonding?
Internal plastic pipes do not need bonding because they are not conductive. However, the main bonding must still be connected where metallic services enter the building — even if the pipes transition to plastic inside. If the entire service is plastic from the street, bonding for that service is not required, but this should be verified by your electrician.
Can I do earthing and bonding work myself?
No. Earthing and bonding are safety-critical aspects of your electrical installation. Incorrect work can create dangerous conditions — including making metalwork live or preventing protective devices from operating in a fault. This work must be carried out by a qualified electrician who can test and verify the installation.

Find earthing & bonding near you

Browse qualified electricians for earthing & bonding by London borough.

Need earthing & bonding?

Describe what you need to Sparky and we'll match you with a qualified electrician near you.

Book an Electrician

It's easier in the app

Download Sparky to request help, track your electrician, and pay securely — all from your phone.

Download on the App StoreGet it on Google Play
Track your confirmed electrician booking in the Sparky app